Fluke 1555 FC

Product name

Product overview: The Fluke 1555 insulation resistance tester offers digital insulation testing up to 10 kV, making it ideal for testing high voltage equipment including switchgear, motors, generators and cables.

What's in the box:

  • Quickly configure, start and stop tests on the 1555 remotely, a safe distance away from any operating, energized equipment, using Fluke Connect® and a smart phone
  • Real time trending gives you easy-to-see visual cues, rather than hard to read, rapidly changing values
  • Report creation using Fluke Connect desktop saves time and makes test results easier to understand
  • Fluke Connect saves test results to the cloud for analysis and preventive maintenance

Specifications: Fluke 1555 FC 10 kV Insulation Tester

Electrical Specifications
The tester's accuracy is specified for one year after calibration at operating temperatures of 0°C to 35°C. For operating temperatures outside the range (-20°C to 0°C and 35°C to 50°C), add ±.25% per °C, except on the 20% bands add ±1% per °C.
Insulation Resistance Measurement
Test voltage (DC)
250 VRange< 250 kΩ,
250 kΩ to 5 GΩ
5 GΩ to 50 GΩ
> 50 GΩ
Accuracy (± reading)Unspecified
5%
20%
Unspecified
500 VRange< 500 kΩ
500 kΩ to 10 GΩ
10 GΩ to 100 GΩ
> 100 GΩ
Accuracy (± reading)Unspecified
5%
20%
Unspecified
1000 VRange< 1 MΩ
1 MΩ to 20 GΩ
20 GΩ to 200 GΩ
> 200 GΩ
Accuracy (± reading)Unspecified
5%
20%
Unspecified
2500 VRange< 2.5 MΩ
2.5 MΩ to 50 GΩ
50 GΩ to 500 GΩ
> 500 GΩ
Accuracy (± reading)Unspecified
5%
20%
Unspecified
5000 VRange< 5 MΩ
5 MΩ to 100 GΩ
100 GΩ to 1 TΩ
> 1 TΩ
Accuracy (± reading)Unspecified
5%
20%
Unspecified
10000 VRange< 10 MΩ
10 MΩ to 200 GΩ
200 GΩ to 2 TΩ
> 2 TΩ
Accuracy (± reading)Unspecified
5%
20%
Unspecified
Bar graph range0 to 1 TΩ (1550C) - 0 to 2 TΩ (1555)
Insulation test voltage accuracy-0%, +10% at 1 mA load current
Induced AC mains current rejection2 mA maximum
Charging rate for capacitive load5 seconds per μF
Discharge rate for capacitive load1.5 s/μF
Leakage current measurementRange1 nA to 2 mA
Accuracy±(5% + 2 nA)
Capacitance measurementRange0.01 μF to 15.00 μF
Accuracy±(15% rdg + 0.03 μF)
TimerRange0 to 99 minutes
Resolution setting1 minute
Resolution indication1 second
Live circuit warningWarning range30 V to 660 V AC/DC, 50/60 Hz
Voltage accuracy±(15% + 2 V)
Software specificationsFlukeView Forms™ basic software requires a PC running Windows XP, Windows Vista , Windows 7 or Windows 8.
General Specifications
Display75 x 105 mm
Power12 V lead-acid rechargeable battery, Yuasa NP2.8-12
Charger Input (AC)85 V to 250 V AC 50/60 Hz 20 VA
This Class II (double insulated) instrument is supplied with a Class 1 (grounded) power cord. The protective earth terminal (ground pin) is not connected internally. The extra pin is for added plug retention only.
Dimensions269 x 277 x 160 mm (10.6 x 10.9 x 6.3 in)
Weight3.7 kg (8.2 lb)
Temperature (operating)-20°C to 50°C (-4°F to 122°F)
Temperature (storage)-20°C to 65°C (-4°F to 149°F)
Humidity80% to 31°C decreasing linearly to 50% at 50°C
Altitude2000 m
Enclosure sealingIP40
Input overload protection1000 V AC
Electromagnetic compatibilityEN 61326
Safety complianceIEC 61010-1: Overvoltage category II, Pollution Degree 2.
IEC 61010-2-030: Measurement 600V CAT IV / 1000V CAT III
IEC 61557-1, IEC 61557-2