Fluke Norma 6000 Series Portable Power Analyzers

Product name

Product overview: Fluke Norma 6000 Series Portable Power Analyzers

What's in the box:

  • Measure voltage, current, active power, reactive power, apparent power, power factor and harmonics with associated values
  • Get accurate, precise results with 0.1% measurement accuracy and a 500kHz bandwidth
  • Take precision power measurements almost anywhere – highly portable, battery powered analyzer weighing only 3.5kg with up to 10 hours of battery life

Specifications: Fluke Norma 6000 Series Portable Power Analyzers

InputsNorma 60033 Voltage + 3 Current
Norma 6003+3 Voltage + 3 Current + 1 Motor
Norma 60044 Voltage + 4 Current
Norma 6004+4 Voltage + 4 Current + 1 Motor
Sample rate200ks/s
Measurement update rate100ms, 200ms, 500ms, 1s
Dimensions (H * W * L)298mm x 215m x 96mm
Weight3.5 kg (7.7 lbs)
Display5.7 inch, TFT LCD, 640x480
Operating temperature-10 °C to +50 °C
Storage temperature-30 °C to +60 °C
Operating humidityNon-condensing (< 10 °C )
≤ 90 % RH (at 10 °C to 30 °C)
≤ 75 % RH (at 30 °C to 40 °C)
≤ 45 % RH (at 40 °C to 50 °C)
Operating altitude2000m
Storage altitude12000m
Ingress protectionIP 50 (Terminals mated) according to IEC 60529:
BatteryBP 291, 10.8V/5000mAh, 54Wh IEC 62133, UN38.3
Operating time: 10 Hours (on battery)
SafetyIEC 61010-1: Pollution Degree 2
IEC 61010-2-030: CAT IV 600V, CAT III 1000 V
EMCIEC 61326-1: Industrial
IEC 61326-2-2
Warranty1 Year
Communication InterfaceUSB/RS485
Dual Analyzer Synchronization ModeAble to extend to 6, 7 or 8 channels (using multiple instruments)
PC SoftwareFluke Power Analyzer software
Storage Capacity32GB
Data trend storage rateAs per display rate
Main FunctionMeter, Scope, Harmonic, Phasor, Trend
Measuring ParametersRMS, DC Component, AC Component, Rectified Mean, Peak Value, Peak-Peak, Crest Factor, Form Factor, Fundamental Component, Fundamental Content, Harmonic Distortion, Harmonic Content, Harmonic Factor for voltages and currents, Active Power, Reactive Power, Apparent Power, Power Factor, Phase Shift, Efficiency, Impedance, Electric Energy, Charge/Discharge capacity (Ah), Frequency, Motor Speed, Torque, Mechanical Power, Mechanical Energy, Summation function
Electrical Specifications
Voltage
Range10 V, 100 V, 1000 V
Crest FactorCF ≤ 2
Maximum Voltage10 % overload
Input Impedance2M Ω/10pF (Typical)
Temperature Coefficient0.05 * (Spec)/k
Bandwidth1000V range: 500kHz; 100V range: 200 kHz; 10V range:100 kHz
CMRR120 dB @ 50/60 Hz
Accuracy (% reading + % range)
Range1000 V100 V10 V
DC0.1 + 0.10.1 + 0.10.1 + 0.2
AC (10Hz to 1kHz)0.1 + 0.10.1 + 0.10.1 + 0.2
AC (10kHz)5 + 0.55 + 0.55 + 0.5
Current
Crest FactorCF ≤ 2
Temperature Coefficient0.05 x (Spec)/k
Overload capacity10 % overload
CMRR120 dB @ 50/60 Hz
Shunt (current input)
Measuring Range0.1 A, 1 A, 10 A
Input Impedance0.025 Ω (Typical)
Bandwidth10 A range: 500 kHz; 1 A range: 200 kHz; 0.1 A range: 100 kHz
BNC (voltage input)
Range0.1 V, 1 V, 10 V
Input Impedance100k Ω/100pF (Typical)
Bandwidth10 V range: 500 kHz; 1 V range: 200 kHz; 0.1 V range: 100 kHz
Accuracy (% reading + % range)
Range10 A1 A0.1 A10 V1 V0.1 V
DC0.1 + 0.20.1 + 0.50.1+20.1+0.10.1+0.20.1+1
AC (10Hz to 1kHz)0.1+0.10.1+0.20.1+10.1+0.10.1+0.10.1+0.5
AC (10kHz)5+15+15+15+15+15+1
Motor Module (Torque and Speed)
Voltage Range± 10 V dc, 10 % overload
Voltage Channels2
Input Impedance1.1M Ω (Typical)
Accuracy at dc0.1 % range + 0.1 % reading
Pulse Channels3
Pulse Logic High Threshold2 V (Typical)
Pulse Logic Low Threshold0.8 V (Typical)
Maximum Pulse Frequency100 kHz
Motor Module (Torque and Speed)
Frequency Accuracy0.05 % range + 0.05 % reading
Harmonics100 (50Hz/60Hz)
Calculation methodFFT/Interpolation